Camille Bauer SINEAX Electrical Power Measurement

Camille Bauer SINEAX multifunctional heavy-current transducers are programmable and may be used for the measurement of almost all quantities of an electrical power system. The application (system configuration) as well as the behaviour of the analog and digital outputs are software configurable. The measurand acquisition via programming or bus interface during normal operation is also supported.

SINEAX Multi-Function Power Meters & Transducers SINEAX Power Transducers
SINEAX Current Transducers SINEAX Voltage Transducers
SINEAX Phase Angle (Power Factor) Transducers SINEAX Frequency Transducers

SINEAX Multi-Function Power Meters & Transducers

A210 & A220 Multifunction Power Meters

Measurement of current, voltage, active, reactive and apparent power, active and reactive energy, neutral conductor current, power factor and frequency
EMMOD

Input:

Single or 3-Phase, 0-1 A to 0-6 A
290 V phase-to-neutral
500 V phase-to-phase
50/60 Hz
Output: Programmable Digital Pulse Relay
  • A210 1/4 DIN size or A220 Full-Size DIN
  • 19 Types of Measurements Including
  • P, Q, S, I~, U~ (rms), cos φ, (PF, 4 quadrants), f, Pint, Qint, Sint
  • 3 Variable Display
  • Open Collector Alarm Relay and Pulse Outputs
  • Data Logging and MODBUS with EMMOD 201 Option
  • Two Analog Outputs with EMMOD 202 Option
  • Ethernet Interface with EMMOD 203 Option
  • PROFIBUS Interface with EMMOD 204 Option
  • Hi/Lo Electrical Rates
  • Includes RS-232 Measurement & Configuration Software
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications   Instructions  EMMOD  MODBUS

A230 & A230s Multifunction Power Meter w. System Load & Harmonics

Measurement of current, voltage, active, reactive and apparent power, active and reactive energy, neutral conductor current, power factor and frequency

EMMOD

Input:

Single or 3-Phase, 0-1 A to 0-6 A
290 V phase-to-neutral
500 V phase-to-phase
50/60 Hz
Output: Programmable Digital Pulse Relay
  • A230 Full-Size DIN or A230s 1/4 DIN
  • 19 Types of Measurements Including
  • P, Q, S, I~, U~ (rms), cos φ (PF, 4 quadrants), f, Pint, Qint, Sint, THD, harmonics, UNE, unbU
  • Three 4-digit Programmable Displays
  • Open Collector Alarm Relay and Pulse Outputs
  • Data Logging and MODBUS with EMMOD 201 Option
  • Two Analog Outputs with EMMOD 202 Option
  • Ethernet Interface with EMMOD 203 Option
  • PROFIBUS Interface with EMMOD 204 Option
  • Hi/Lo Electrical Rates
  • Comprehensive mean and max./min. value functions with trend
  • System analysis functions (THD, harmonics, asymmetry)
  • Includes RS-232 Measurement & Configuration Software
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications   Instructions  EMMOD  MODBUS

SIRAX BM1200, BM1400, BT5700, MM1200, MM1400, Programmable, Multifunctional Monitors




Input:

57 - 288 VLN
45 - 50/60 - 65 Hz
60 - 300 V AC/DC
Output: RS485 (Modbus RTU) Ethernet (Modbus TCP)
  • Well-visible one-line indication of measured data with backlit LCD display
  • Easy on-site operation and parameterisation
  • Automatic cyclical scrolling of measured data
  • Integrated active and reactive energy meters, cost-effective alternative to energy meters

 

 

 

 

 

Specifications   Instructions 

SIRAX MT7000/MT7050, AC/DC Current and Voltage Converter/Analyzer




Input:

Current transformer with secondary 1A/5A
Current and voltage transformer with secondary ±10 Vpk or ±1 Vpk
Current transformer with secondary 100 mAAC/DC; Hall effect sensor ±15 VDC (incl. power supply)
Output: RS485 Modbus/RTU
  • Break-resistant plastic housing made of PBT
  • Flame retardant and self extinguishing according to UL94 V0
  • Common current and voltage transformers, Rogowski coils and temperature sensors can be connected
  • Configuration by configuration software
  • Serial RS485 Modbus/RTU output
  • DIN rail or wall mounting for vertical or horizontal position

 

 

 

 

 

Specifications   Instructions 

SINEAX AM1000, AM2000, AM3000 Multifunctional Power Monitor




Input:

  • 4 S0 digital inputs active
  • 4 S0 digital inputs passive
  • Temperature Inputs: Measurement sensor Pt100 / PTC
Output:
  • 2 relay outputs
  • 2 analog outputs ±20mA?
  • 4 analog outputs ±20mA
  • Direct measurement up to 690V, CATIII?
  • Class 0.2 (U/I), class 0.5 (P/Q/S), class 1.0 (meters)
  • Condition monitoring?
  • Energy consumption analysis (Meters, load curves, trend analysis)?
  • Harmonic analysis acc. IEC 61000-4-7?
  • System imbalance monitoring?
  • Limit monitoring with alarming?
  • Universal process I/O?
  • Graphical measurement displays?
  • High resolution color TFT display
  • Standard I/Os (1 digital output, 1 digital input/output)

 

 

Specifications   Instructions 

LINAX PQ3000, PQ5000 Multifunctional Power Quality Monitor




Input:

  • 4 S0 digital inputs active
  • 4 S0 digital inputs passive
  • Temperature Inputs: Measurement sensor Pt100 / PTC
Output:
  • 2 relay outputs
  • 2 analog outputs ±20mA?
  • 4 analog outputs ±20mA
  • Certified power quality analysis, class A acc. IEC 61000-4-30 Ed. 3
  • Standardized data format for power quality data: PQDIF
  • Energy consumption analysis, class 0.5S (meters, load profiles, trend analysis)
  • EN50160 conformity reports via SMARTCOLLECT PM20
  • On-site event display
  • Direct measurement up to 690V, CATIII
  • Condition monitoring
  • Limit monitoring with alarming
  • Universal process I/O
  • Graphical measurement displays
  • High resolution color TFT display
  • Standard I/Os (1 digital input, 2 digital outputs
Specifications   Instructions 

CENTRAX CU3000, CU5000 Power Measurement Device With PLC Functionality




Input:

  • 4 S0 digital inputs active
  • 4 S0 digital inputs passive
  • Temperature Inputs: Measurement sensor Pt100 / PTC
Output:
  • 2 relay outputs
  • 2 analog outputs ±20mA?
  • 4 analog outputs ±20mA
  • Modbus/RTU interfac
  • Direct measurement up to 690V, CATIII?
  • Condition monitoring: class 0.1 (U/I), class 0.2 (P/Q/S)?
  • Energy consumption analysis, class 0.5S (meters, load profiles, trend analysis)?
  • Harmonic analysis acc. IEC 61000-4-7?
  • System imbalance monitoring?
  • Universal process I/O?
  • Graphical measurement displays?
  • High resolution color TFT display?
  • Standard I/Os (1 digital input, 2 digital outputs)

 

Specifications   Instructions 

Sineax A-Plus True RMS Multifunction Power Meter with Power Quality Analysis

Input:

Single or 3-Phase, 0-1A to 0-6 A
400 V phase-to-neutral
690 V phase-to-phase
50/60 Hz

Output:

Programmable
1 Digital Pulse
1  Relay
MODBUS


  • Power quality analysis
  • Display 4 variables
  • MODBUS standard
  • Optional 2 relay and 4 analog outputs, 2 digital I/O
  • Optional 2 relay, 6 digital I/O
  • Optional data logging
  • Alarm contact triggered on any setpoint
  • Includes measurement & configuration software
  • 100-230 VAC or 24-230 VDC powered
A Plus Brochure    A Plus Instructions
A Plus Modbus    A Plus Modbus/TCP

A2000 True RMS Multifunction Power Meter

Input:

Single or 3-Phase, 0-1A to 0-6 A
290 V phase-to-neutral
500 V phase-to-phase
50/60 Hz

Output:

Programmable
4  Analog
2  Digital Pulse
2  Relays
  • Display 4 Variables
  • Up to 4 Analog and 2 Pulse Outputs
  • Data Logging of any of 37 Values
  • 2 Relay Outputs
  • Alarm Contacts Triggered on any Setpoint
  • Includes Measurement & Configuration Software
  • MODBUS / LONBUS / PROFIBUS Versions
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

M 563 Power & Current Transducer

Input:

0-1 A to 0-6 A
57-400 V phase-to-neutral
100-693 V phase-to-phase
50 or 60 Hz

Output:

0-20 mA, 4-20 mA
0-1 V to 0-10 V
2-10 V

  • 3 Analog Outputs
  • Measures any Three: P, Q or S, I ~, U ~ (RMS), cos j, sin j, LF, PF, QF, f
  • RS 232 PC Programming Interface
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

Sineax CAM Multifunction Energy Transducer

Input:

0-1A, 0-5 A or
Two 4-20 mA
57-400 V phase-to-neutral
100-693 V phase-to-phase
50/60 Hz
Digital I/O

Output:

RS-485 MODBUS interface
USB 2.0
Relay
Up to 4 analog
Digital I/O



  • True RMS
  • Simultaneous measurement of all 3 phases
  • Measures P, Q or S, I ~, U ~ (RMS), cos f, sin f, LF, PF, QF, LF, f, THD, TDD, VAR
  • USB programming interface
  • 85-265 VAC/ 110-265 VDC powered
  • Optional 17-90 VDC powered
CAM Specifications    CAM Instructions
MODBUS Instructions

SIRAX BT5100, BT5200, BT5300, BT5400, Basic Transducers

Input:

57 - 500 V
57 - 400 kV
45 - 65 Hz
50/60 Hz

Output:

RS-485 MODBUS/RTU interface
0 - 20 mA / 4 - 20 mA or 0 - 10 V



  • One-phase connection (Voltage)
  • 2 configurable analog outputs linear or kinked in a range from 0/4…20 mA, 0/2…10 V
  • Quick on-site programming using push buttons or via CB-Configurator software
  • Simple on-site device operation
  • Clear and well readable representation of measured data via LCD display
  • Flexible communication and remote readout via integrated Modbus RTU interface
  • DIN rail for top-hat rail mounting
Specifications    Instructions

SINEAX DM5S & SINEAX DM5F

Input:

Adjustable 1 - 5 A
≤ 12 x 0.01 Ω per phase

100 - 230 V AC

Output:

Linear or kinked

± 20 mA (24 mA max.), bipolar

RS-485, max. 1200 m (4000 ft)



  • System state monitoring: class 0.2
  • DM5S: Energy metering: class 0.5S
  • DM5F: Response time 15 - 25ms
  • Assisted commissioning
  • Configuration even without power supply
  • Certifications: UL
Specifications    Instructions

SINEAX DM5000, Multifunctional Power Monitoring Device

Input:

4 S0 digital inputs active

4 S0 digital inputs passive

Temperature Inputs: Measurement sensor Pt100 / PTC?


Output:

2 relay outputs

2 analog outputs ±20mA?

4 analog outputs ±20mA




  • Direct measurement up to 690V, CATIII
  • Condition monitoring: class 0.1 (U/I), class 0.2% (P/Q/S)
  • Energy consumption analysis, class 0.5S (meters, load profiles, trend analysis)
  • Harmonic analysis acc. IEC 61000-4-7
  • System imbalance monitoring
  • Limit monitoring with alarming
  • Universal process I/O
  • Communication via Ethernet and Modbus/RTU
  • Standard I/Os (1 digital input, 2 digital outputs)
Specifications    Instructions

Sineax A200 Multifunction Display for DME Power Transducers

Input:

Serial data from DME4 series

Output:

3 digital displays



  • 1/4 DIN (96 x 96 mm) display for DME4 transducers
  • Triple LED display 14 mm digit height
  • Selectable display parameters
  • 20-265 VAC/VDC powered
A200 Specifications    A200 Instructions




DME 424 & DME 442 Energy Transducers

Input:

0-0.8 A to 0-1.2 A or
0-4 A to 0-6 A
57-400 V phase-to-neutral
100-693 V phase-to-phase
50/60 Hz

Output:

0-20 mA, 4-20 mA
0-1 V to 0-10 V, 2-10 V
Open Collector Pulse

  • DME 424 with 2 analog and 4 digital pulse outputs
  • DME 442 with 4 analog and 2 digital pulse outputs
  • Measures P, Q or S, I ~, U ~ (RMS), cos j, sin j, LF, PF, QF, f
  • Data Logging Function
  • RS 232 PC Programming Interface
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions


SINEAX Power Transducers

P 530 Active Power & Q 531 Reactive Power Transducers

Input:

0-0.8 A to 0-1.2 A or
0-4 A to 0-6 A
100-690 V
50/60 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
1 mA to 20 mA
0-1 V to 2-10 V, to 10 V


  • 3-Phase with Balanced or Unbalanced Load
  • Sinusoidal Input
  • Available as Measuring Source Powered to 230 V
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

Sineax M 561 Power & Current Transducer

Input:

0-1 A to 0-6 A
57-400 V phase-to-neutral
100-693 V phase-to-phase
50 or 60 Hz

Output:

One analog output
0-20 mA, 4-20 mA
0-1 V to 0-10 V
2-10 V


  • 1 analog output
  • Measures any One: P, Q or S, I ~, U ~ (RMS), cos f, sin f, LF, PF, QF, f
  • RS 232 PC programming interface
  • 24-60 VAC/VDC or 85-230 VAC/VDC powered
M 560 Series Specifications    M 560 Series Instructions

Sineax M 562 Power & Current Transducer

Input:

0-0.8 A to 0-1.2 A or
0-4 A to 0-6 A
100-690 V
50/60 Hz

Output:

2 analog outputs
0-20 mA, 4-20 mA
0-1 V to 0-10 V
2-10 V


  • 2 analog outputs
  • Measures any two: P, Q or S, I ~, U ~ (RMS), cos f, sin f, LF, PF, QF, f
  • RS 232 PC programming interface
  • 24-60 VAC/VDC or 85-230 VAC/VDC powered
M 560 Series Specifications    M 560 Series Instructions

Sineax M 563 Power & Current Transducer

Input:

0-0.8 A to 0-1.2 A or
0-4 A to 0-6 A
100-690 V
50/60 Hz

Output:

3 analog outputs
0-20 mA, 4-20 mA
0-1 V to 0-10 V
2-10 V


  • 3 analog outputs
  • Measures any Three: P, Q or S, I ~, U ~ (RMS), cos f, sin f, LF, PF, QF, f
  • RS 232 PC programming interface
  • 24-60 VAC/VDC or 85-230 VAC/VDC powered
M 560 Series Specifications    M 560 Series Instructions


SINEAX Current Transducers

I 538 AC Current Transducer

Input:

0-0.8 A to 0-1.2 A or
0-4 A to 0-6 A
50/60 Hz

Output:

0-20 mA, 4-20 mA
0-1 V to 0-10 V, 2-10 V

  • Sinusoidal Input
  • Available as Measuring Source Powered to 230 V
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications   Instructions

I 542 AC Current Transmitter

Input:

0-0.8 A to 0-1.2 A or
0-4 A to 0-6 A
50/60 Hz

Output:

0-20 mA, 4-20 mA
0-1 V to 0-10 V, 2-10 V

  • Sinusoidal Input
  • Powered from Measuring Source

Specifications   Instructions

I 552 True RMS AC Current Transducer

Input:

0-0.8 A to 0-1.2 A or
0-4 A to 0-6 A
50/60 or 400 Hz

Output:

0-20 mA, 4-20 mA
0-1 V to 0-10 V, 2-10 V

  • Sine, Rectangular or Distorted Wave Forms
  • Available as Measuring Source Powered to 230 V
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

SINEAX Voltage Transducers

U 539 AC Voltage Transducer

Input:

0-50 V to 0-600 V
50/60 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
0-1 V to 2-10 V



  • Sinusoidal Input
    Available as Measuring Source Powered to 230 V
    24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

U 543 AC Voltage Transducer

Input:

0-20 V to 0-600 V
50/60 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
0-1 V to 2-10 V


  • Sinusoidal Input
  • Powered from Measuring Source

Specifications  Instructions

U 553 True RMS AC Voltage Transducer

Input:

0-20 V to 0-690 V
50/60 or 400 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
0-1 V to 2-10 V


  • Sine, Rectangular or Distorted Wave Forms
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

U 554 True RMS AC Voltage Transducer

Input:

0-20 V to 0-690 V
50/60 or 400 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
0-1 V to 2-10 V


  • Sine, Rectangular or Distorted Wave Forms
  • Special Version to Allow Zero Offset

  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

SINEAX Frequency Transducers

F 534  Frequency Transducer

Input:

10 V to 690 V
10 to 1500 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
1 mA to 20 mA
0-1 V to 2-10 V, to 10 V


  • Sine, Rectangular or Distorted Wave Forms
  • Available as Measuring Source Powered to 230 V
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

F 535 Frequency Difference Transducer

Input:

10 V to 690 V
10  to 1500 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
1 mA to 20 mA
0-1 V to 2-10 V, to 10 V


  • Measure Δf Between 2 Synchronized Supplies
  • Sine, Rectangular or Distorted Wave Forms
  • Available as Measuring Source Powered to 230 V
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

SINEAX Phase Angle (Power Factor) Transducers

G 536 Phase Angle Transducer

Input:

1 or 5 A
10 V to 690 V
16 to 400 Hz
0.5 cap. 1.ind. 0.5 cos Φ

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
1 mA to 20 mA
0-1 V to 2-10 V, to 10 V


  • Measure Single or 3-Phase Balanced
  • Sine, Rectangular or Distorted Wave Forms
  • Available as Measuring Source Powered to 230 V
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions

G 537 Phase Angle Difference Transducer

Input:

10 V to 690 V
50 or 60 Hz

Output:

0-1 mA to 0-20mA
1-5 mA to 4-20 mA
1 mA to 20 mA
0-1 V to 2-10 V, to 10 V


  • Measure ΔΦ Between 2 Synchronized Supplies
  • Sine, Rectangular or Distorted Wave Forms
  • Available as Measuring Source Powered to 230 V
  • 24-60 VAC/VDC or 85-230 VAC/VDC Powered
Specifications    Instructions



青娱乐视频精品国产,国产精品在线超碰视频在线,国产精品福利再战